| Laars EBP110 Endurance Hydronic Boiler w. Domestic Hot Water Item Number: 11720 Manufacturer Name: Laars Heating Systems Company Manufacturer Part No: EBP110 | | Laars EBP110 Endurance Hydronic Boiler w. Domestic Hot Water Specifications: - Input (MBTU/h): 61.8-108.2
- Input (kW): 18.1-31.7
- Output (MBTU/h): 53.7-94.0
- Output (kW): 15.7-27.5
- AFUE%: 85.5
- Continuous GPH @ 100 F Rise: 114
- Minimum Clearances from Combustible Materials:
- Back & Front: 1"
- Sides: 1"
- Top (Alcove Install): 1"
- Top (Closet Install): 22"
- Vent: Concentric, Direct: 0"
- Vent: Category IV: 3"
Features: - Design certified and tested to ANSI standard Z21.13
- Designed and constructed in accordance with the ASME Boiler & Pressure Vessel Code, Sections II, IV, and IX
- Maximum working pressure - water 30 psi, ASME rated
- Hydrostatic test pressure at factory - 60 psi
- Minimum gas supply pressure - 4" w.c.
- Maximum gas supply pressure - 13" w.c.
- 85+% AFUE
- Sealed stainless steel combustion chamber
- Hot surface ignition
- Automatic burner modulation from 57% to full fire
- NOx levels less than 25 ppm
- Venting - Direct vent (sealed combustion with ducted combustion air in concentric vent) or Category III
- Design certified for installation directly on a combustible floor (except carpeting)
- One-inch clearance on all 4 sides
- Zero clearance from combustibles to the vent when concentric venting is used
- Electrical: 115V-60HZ-1PH less than 15 Amps with 24V transformer mounted and wired
- Outdoor reset with the addition of outdoor air sensor (limited temperature range available for EBP models)
- Control overrides outdoor reset when air sensor is faulty
- Easy-to-use viewing and programming menus
- 3-Character alphanumeric display of temperatures and fault codes
- Displays fault codes for supply sensor, return sensor, tank sensor (EBP only), outdoor air sensor, internal control, and lockout
- Displays 6 temperatures: supply water, return water, tank water (EBP only), heatexchanger temperature rise, outdoor air temperature (when outdoor resetis used), and calculated setpoint (when outdoor reset is used)
- Controls LEDs indicated pump energized, attempt to ignite and gas valve energized
- Ignition control LEDs show faults for erroneous flame signal, internal error and lockout
- Low water temperature feature - attempts to run the pump when supply water temperature falls below 39 F
- Built-in circulating pump and by-pass loop
- Equipped with anti-condensing controls
- Pump exerciser to ensure pump remains free from corrosion
- Built-in safety limit
- Copper finned, cylindrical tube design heat exchanger brazed into ASME bronze headers
- EBP unitedstore 20 gallons of boiler water to provide instantaneous domestic hotwater production through a brazed plate heat exchanger, with DHWpriority
-
20 Year limited warranty For more information on this product please view the Sheet(s) below: Laars Endurance EBP, EDP, EDN Installation Manual Laars Endurance Parts List Laars Endurance Questions And Answers Booklet | Laars 30-119 1/2" Gasket Laars 30-119 1/2" Gasket | Laars 36-288 Control Board Standoff Clip Laars 36-288 Control Panel Locking Standoff Clip | Laars 30-105 Gasket, 3/4" Nut Laars 30-105 Gasket, 3/4" Nut | Laars 30-103 Gasket, 1" Nut Laars 30-103 Gasket, 1" Nut | Laars 10-916 Spring Laars 10-916 Spring | Laars 30-616 Line Voltage Fuse Laars 30-616 Line Voltage Fuse | Laars A2108100 Plastic Blower Cover Laars A2108100 Plastic Blower Cover | Laars 2400-437 5" Support Clamp Laars 2400-437 5" Support Clamp | Laars 2400-528 Gasket Laars 2400-528 Gasket, for Ignitor | Laars 2400-304 3" Spring Support Laars 2400-304 3" Spring Support | Laars 1-580 Flow Restrictor Laars 1-580 Flow Restrictor | Laars 2400-282 Silicone Sealant Laars 2400-282 Silicone Sealant | Laars 2400-281 Rubber Wall Flange Laars 2400-281 Rubber Wall Flange, 5" Diameter | Laars 2400-426 3" Terminal W/ Screen Laars 2400-426 3" Terminal W/ Screen | Laars 2400-280 Steel Wall Flange Laars 2400-280 Steel Wall Flange, 5" Diameter | Laars 2400-349 2nd 90 Elbow Laars 2400-349 2nd 90 Elbow, 5" Stainless Steel, Male x Female | Laars 2400-332 Vent Intake Pipe Laars 2400-332 Vent Intake Pipe, 5" x 1' Stainless Steel | Laars 2400-540 Gasket, Blower Laars 2400-540 Gasket, Blower | Laars 2400-112 Pressure Relief Valve Laars 2400-112 Pressure Relief Valve, 30 psi | Laars 2400-514 Burner Gasket Laars 2400-514 Burner Gasket | Laars 2400-372 Alternate Vent Clamp Laars 2400-372 Alternate Vent Clamp | Laars 2400-356 5" Stainless Steel 45 Elbow Laars 2400-356 5" Stainless Steel 45 Elbow, 5" Stainless Steel, Male x Female | Laars 2400-347 1st 90 Elbow Laars 2400-347 1st 90 Elbow, 5" Stainless Steel | Laars 2400-572 Gaskets, DHW Heat Exchanger Laars 2400-572 Gaskets, DHW Heat Exchanger | Laars 2400-338 Vent Exhaust Pipe Laars 2400-338 Vent Exhaust Pipe, 3" x 1' (SS AL29-4C) | Laars 2400-029 Thermostat & O Ring Laars 2400-029 Thermostat & O Ring, for 1 1/4" Thermostatic Union | Laars 2400-146 Gas Orifice Kit Laars 2400-146 Gas Orifice Kit, High Altitude | Laars 2400-446 Return Sensor Laars 2400-446 Return Sensor | Laars 2400-522 Boiler Drain Laars 2400-522 Boiler Drain | Laars 2400-568 Reset Switch Laars 2400-568 Reset Switch | Product Reviews | | |